Appendix C
Interface Cable Requirements
OPS Series
Signal Twisted Pair
A+ Pair 1
A-
B+ Pair 2
B-
Index+ Pair 3
Index-
+5V Pair 4
GND
Left Limit Pair 5
Right Limit
1. Customer Interface Cable Requirements
Customer cables that interface to OPS
series encoders must have the following characteristics:
Twisted pair signal wiring.
Characteristic impedance of 100-120 ohms.
Sufficient wire gauge to meet the minimum voltage requirement at the encoder, for example 24AWG
gauge wire for a 2m length cable. Examples of acceptable cables with 24AWG gauge wire and 4
twisted pairs are Belden 9831, 8104, and 9844 or other manufacturers equivalents.
Single shield cable with a minimum of 90% coverage. Note that a double shielded cable may be
required in high-noise applications.
2. Signal Wiring
Each differential signal should be connected to a corresponding twisted pair as follows:
Fold braided shield back over jacket. Example shows double-shielded cable.
Dimensions shown are for illustration only.
3. Shield Termination:
The customer's cable shield should be in 360° contact with the connector shroud and the connector shell to
provide complete shielding. The connector shell should be metal with conductive surfaces. Suggested metal
connector shells for use with OPS
encoders: AMP 748676-1 or equivalent. The shield should be terminated
as illustrated in the following diagram.