Page 15
Section C - Reference
Grounding Instructions -
Mercury II
6000
Sensor mounted to a surface that is
grounded through bearings or a poorly-
grounded surface, or mounted to a non-
conducting surface
CC11..22..11
15-pin D-sub connector grounding: The
encoder's connector shell must be in intimate,
electrically conductive contact with the
customer-supplied mating connector, which
must be connected to the controller's ground.
If a customer-supplied shielded cable
connects the encoder to the controller, then
the outer shield on the customer-supplied
cable must be connected to the controller's
ground. The controller must be grounded to
earth at the point of installation.
CC11..22..22
The encoder sensor must be mounted so that
it is electrically isolated from ground.
5 Volts
0 Volts
POWER
SUPPLY
Zobrazit stránku 14